Insulation materials for transformers, motors & reactors · Since 2008 ✉ liuxinlx521@gmail.com WhatsApp +8615690899924
Transformer Insulation Materials

Diamond Dotted AMA

Cable paper / polyester film laminate with diamond-pattern adhesive, Class B

Diamond Dotted AMA product photo - Transformer Insulation supplied by Hengsheng Technology
Diamond Dotted AMA · image placeholder - replace with your product photo

A cable paper / PET film laminate with a diamond-pattern adhesive that cures into a stable bond after 140°C heat treatment. Designed for HV-LV interlayer insulation in oil-immersed transformers.

Class B (130°C)Thickness 0.15 / 0.20 mmAdhesive strength 820 kPa
Temperature class
Class B (130°C)
Thickness
0.15 mm / 0.20 mm
Breakdown voltage
8.1–12.5 kV
Curing
140°C / 3–4 h
Request a quotation or a sample. Tell us thickness, width, temperature class, quantity and delivery form. We reply within one business day.

Request a Quote WhatsApp Us

Technical data

Diamond dotted AMA - datasheet values (catalogue, p.08)
PropertyUnitValue
Thicknessmm0.15 / 0.20
Adhesive strength, normalkPa820
Breakdown voltage, normal oil (ø25 mm / ø75 mm electrode, rapid boost)kV8.1–12.5
Breakdown voltage after bendingkV11.65–13.33
Power-frequency withstand (120°C ±2°C, 15 min)—6 kV and 8 kV passed
Dielectric constant—2.42
Dielectric loss factor (120°C ±2°C)—2.58×10⁻³ / 3.19×10⁻³
Pollution of transformer oil—<0.001 (8.0×10⁻³)
Fixed quantityg/m²180±5% / 230±5%
Curing conditions—140°C, 3–4 h
Temperature class—Class B (130°C)

Values are typical values or ranges from our product data. Bulk supply is subject to the approved specification, sample and test report. If a parameter you need is not listed here, ask our engineers for the full test report for that grade.

Key features

  • Combines the oil affinity of cable paper with the dielectric strength of PET film.
  • Double-sided adhesive layers cure into a stable bond for continuous lamination and winding.
  • Reduces process steps and improves productivity compared with conventional cable-paper bonding.

Applications

HV/LV interlayer insulation in oil-immersed power transformers and distribution transformers.

Oil-Immersed TransformersDistribution Transformers

Why it fits

Where cable paper alone is not enough, the PET core raises dielectric strength at a wall thickness the winding design already uses.

Ordering information

To receive a quotation, please confirm:

  • Product and grade
  • Thickness and width (and roll or sheet size)
  • Temperature class
  • Quantity and delivery form (roll / sheet / die-cut / machined)
  • Destination port and required delivery date

For machined parts, attach a drawing in PDF, DWG or STEP format. Datasheets, COAs and batch test data are available on request.

Related materials

Often specified together

Send your specification

Our export team reviews the application, the process and the existing specification before recommending a construction.

Send an Inquiry