Insulation materials for transformers, motors & reactors · Since 2008 ✉ liuxinlx521@gmail.com WhatsApp +8615690899924
Transformer Insulation Materials

PET Composite Cowl

Multi-layer polyester film composite board, Class F

PET Composite Cowl (Polyester Film Composite Board) product photo - Transformer Insulation supplied by Hengsheng Technology
PET Composite Cowl (Polyester Film Composite Board) · image placeholder - replace with your product photo

Polyester film composite board built from layers of PET film coated with high-temperature adhesive, for HV-LV inter-coil and end insulation in dry-type transformers.

Class F (155°C)SBFWB-0.5 / SBFWB-1.1Machine-direction ≥350 N/10 mm
Temperature class
Class F (155°C)
Thickness
0.5 / 1.1 mm
Standard width
1000 mm
PET layers
2 / 4
Request a quotation or a sample. Tell us thickness, width, temperature class, quantity and delivery form. We reply within one business day.

Request a Quote WhatsApp Us

Technical data

Polyester film composite board - SBFWB types (catalogue, p.15)
PropertyUnitValue
Type—SBFWB-0.5 / SBFWB-1.1
Normal thicknessmm0.5 / 1.1
Thickness tolerancemm±0.045 / ±0.09
Grammageg/m²622 ±68 / 1120 ±112
PET film thicknessµm250
PET layerslayers2 / 4
Tensile strength MD / TDN/10 mm≥350 / ≥600
Elongation MD / TD%≥30 / ≥30 (0.5 mm); ≥50 / ≥50 (1.1 mm)
Breakdown voltage, unbentkV≥35 / ≥50
Breakdown voltage, after bendingkV≥30 / ≥40
Temperature class—Class F (155°C)

Values are typical values or ranges from our product data. Bulk supply is subject to the approved specification, sample and test report. If a parameter you need is not listed here, ask our engineers for the full test report for that grade.

Key features

  • Multi-layer PET construction allows thickness and dielectric strength to be designed in.
  • A lighter alternative to some epoxy or phenolic boards for inter-coil and end insulation.
  • Standard width 1000 mm; slitting and custom widths available.

Applications

HV-LV inter-coil insulation, insulation cylinders and end insulation in dry-type transformers; reactors.

Dry-Type TransformersReactorsElectric Motors & Generators

Why it fits

For dry-type transformers the composite gives you dielectric strength without the mass and machining cost of a rigid laminate.

Ordering information

To receive a quotation, please confirm:

  • Product and grade
  • Thickness and width (and roll or sheet size)
  • Temperature class
  • Quantity and delivery form (roll / sheet / die-cut / machined)
  • Destination port and required delivery date

For machined parts, attach a drawing in PDF, DWG or STEP format. Datasheets, COAs and batch test data are available on request.

Related materials

Often specified together

Send your specification

Our export team reviews the application, the process and the existing specification before recommending a construction.

Send an Inquiry